Engineered For Performance

Little things make big motors perform better. That's why Continental attends to every detail.

Quality assurance checks begin the moment components or raw materials enter our plant and continue, almost uninterrupted, until completed motors are shipped. Each rotor is dynamically balanced and thoroughly tested. Vibration and noise levels are in accordance with NEMA and IEEE guide lines, or are controlled to meet your safety specifications. Every effort is made to assure optimum performance with minimal repair and maintenance. It's why Continental today supports its motor with the broadest, most comprehensive product warranty in the industry.

DESIGN AND OPERATING FEATURES

Air Gap

The air gap is selected to provide proper mechanical clearance with a reasonably high power factor. The rotors and stators are manufactured to be highly concentric in order to minimize noise and vibration. By combining a relatively large air gap with small slot openings Continental is able to minimize permeance pulsations.

Back to the top


Balance

Standard Continental motors meet or exceed NEMA precision balance definitions. Shafts with rotors are balanced.  Internal fans, if any, are added, and the assembly is rebalanced.  External fans, if any, are added, and the assembly is rebalanced. 
All these balance steps are run with a half  height, full length key.  If the customer supplies a 1/2 coupling, it is mounted utilizing a full height and length key and the entire assembly is rebalanced again.  When the balance process is completed, the assembly will be balanced to 2 oz. in per plane or better in 2 planes.

Back to the top


CECO-Seal

Continental’s CECO-Seal system is optionally available for all winding types and voltages.  This proprietary system is a totally sealed system suitable for testing per IEEE-429.

Back to the top

Corrosion Protection

Continental motors, 40 and 50 years old are routinely found in service testifying to the ruggedness of their construction. Part of the reason for this longevity is the standard processes which provide protection from the elements.

All unassembled parts of the motor are thoroughly cleaned to remove rust, scale, oxidation, and the oil and grease associated with the manufacturing process. 

The stator, after the completion of winding, as an assembly, receives a VPI treatment so that the entire core has a polyester or epoxy coating as a base.
 
After assembly and testing, the exterior of the  motor is again cleaned and receives another coating of water reducible primer.  After the primer has dried, a top coat of a quick dry water reducible enamel is applied, resulting in a total dft of 4-5 mils.

Zinc plated hardware is an option is requested and will certainly increase corrosion protection of any motor.  If the motor is to be used in an H2S atmosphere, the rotor itself will receive a VPI treatment and all exposed leads will be tinned. 

Back to the top


Efficiency (click here for performance table)

High efficiency may be optionally available with other motor manufacturers, but it's standard with Continental. We supplied 95% efficient motors long before they became fashionable, and long before they were mandated.  Continental's standard efficiencies are far superior to the competition with the option available for Premium efficiency if requested.

Back to the top


Insulation

As standard Continental will provide an insulation system rated at Class F with the motor designed for B rise and 1.15 service factor.

While the following information is provided to show our standards we often will modify our approach, increasing the level of protection in order to provide a motor which exceeds the expectations for the individual rating.

Random wound up to 300 HP and 600 VAC
  Wire type – High Poly Thermaleaze
  Slot Liner: Dacron Mylar Dycron (Class F)
  Nomex Mylar Nomex (Class H)
  Top Stick : Dacron Mylar Dacron
  Mid Stick: Dacron Mylar Dacron
  Phase Paper:  Nomex Mylar Nomex 
 

VPI – F rated polyester or epoxy – 1 application standard- CC1305 Solventless Polyester
Resin

  For VFD use….. Spike resistant wire (Q- Thermaleaze)
   
Form Wound –  All Voltages – All coils are manufactured to meet the exact specifications of the product.




   
Form Wound –   Low voltage above 300HP.
  Medium voltage – up to 6,900 VAC
  Coil Type construction – dependent on volts per turn ratios
  High Poly Thermaleaze
  High Poly Thermaleaze with glass coating
  High Poly Thermaleaze with double glass coating
  Completed coil is wrapped with Mica Tape, and Armor tape, number of layers is
voltage and application dependent.
  Slot Liner: Dacron Mylar Dacron (Class F)
  Nomex Mylar Nomex (Class H)
 

Top Stick: Dacron Mylar Dacron

 

VPI – F rated polyester or epoxy – 1 application standard- CC1305 Solventless
Polyester Resin

  For VFD use: Medium voltage VFD’s do not have the same rise times as low voltage
VFD’s.  The CEM standard insulation is suitable for the MV VFD applications high
voltage spike. The coil will have corona shield above 4160 V, 2000 HP.
   
 Form Wound – High voltage up to 13,800 VAC
  Coil Type construction – dependent on volts per turn ratios.
  High Poly Thermaleaze
  High Poly Thermaleaze with glass coating
  High Poly Thermaleaze with double glass coating
  Completed coil is wrapped with Mica Tape, and Armor tape, number of layers is
voltage and application dependent.
  Slot Liner: Dacron Mylar Dacron (Class F)
  Nomex Mylar Nomex (Class H)
  Top Stick : Dacron Mylar Dacron
  VPI – H rated polyester – 1 application standard – CC1305 Solventless
Polyester Resin
  For VFD use: Medium voltage VFD’s do not have the same rise times as low
voltage VFD’s.
  The CEM standard insulation is suitable for the MV VFD applications high voltage
spike. The coil will have corona shield.

                          
Back to the top

 

Lamination Material

Laminations are all single piece and punched from minimum M-22 grade non-oriented electrical steel coated with a C-5 high resistance insulation suitable for burnout up to 801 degrees Fahrenheit.  Dependent on application considerations M19 and M15 grades of steel may be used.

Back to the top

 

Lubrication

Continental's proprietary and patented oil ring lubrication systems are an option in addition to our standard oiling system with all Continental motors. Continental's patented self-contained oil lubricator is mounted on the motor shaft. There is no oil bath, allowing complete lubrication with just 24 ounces of oil, where other systems may require 24 quarts or more.  Because the impellers turn with the shaft, lubrication starts the moment the motor is started.

Continental utilizes various lubrication systems dependent on application and customer requirements. Below are the general descriptions of these systems:


Horizontal
           
Grease
           
Oil – Standard Oil
           
Oil – Continental Electric Motor proprietary
           
Oil - Mist
           
Oil - Forced

Grease- Grease lubricated ball bearings are standard and single shielded to help keep the grease close to the rolling elements.  A grease inlet hose with grease fitting supplies grease directly to the bearing.  A grease outlet pipe with removable plug is provided.

Oil Ring- The oil pumping ring rides directly on the rotor shaft thus delivering oil to the bearings immediately upon startup.  Self-lubricating oiler with oil level viewer is provided.  Drain is provided in oiler. 

Oil Mist- Oil mist motors have an inlet pipe that directs the oil mist directly onto the bearings.  Condensate oil can be relieved via drain plug in the cartridge assembly to prevent lubrication flooding.  Oil mist generator is typically provided by others.

Oil Forced- Forced lubricated motors have an inlet pipe that directs the oil mist directly into the bearing housings.  The return path is provided by an outlet pipe that runs directly to the lubrication generator.  The forced oil system is typically provided by others.


 Vertical
 Grease
           
Oil – standard
           
Oil – Continental Electric Motor proprietary
           
Oil – Tilting Pad
           
Oil - Mist
           
Oil - Forced

Grease- Grease lubricated ball bearings are single shielded to help keep the grease close to the rolling elements.  A grease inlet hose with grease fitting supplies grease directly to the bearing.  A grease outlet pipe with removable plug is provided.

Oil- CEM proprietary impeller- The oil pumping impeller is driven by the rotor shaft thus delivering oil to the bearings immediately upon startup.  Self-lubricating oiler with oil level viewer is provided.  Drain is provided in oiler. 

Oil- Tilting Pad – Oil bath lubricated.  These bearings sit in an oil bath to aid in keeping the bearings cool.  Oil level viewer is provided.  Normally a cooling coil is part of the assembly, sitting in the oil bath.  Coolant is typically water from a city connection, or chiller system, provided by others.

Oil Mist- Oil mist motors have an inlet pipe that directs the oil mist directly on to the bearings.  Condensate oil can be relieved via drain plug in the cartridge assembly to prevent lubrication flooding.  Oil mist generator is typically provided by others.

Oil Forced- Forced lubricated motors have an inlet pipe that directs the oil mist directly into the bearing housings.  The return path is provided by an outlet pipe that runs directly to the lubrication generator.  The forced oil system is typically provided by others.

Anti Friction Bearing Lubrication Selection

Back to the top

 

Magnetic Densities

Flux densities are controlled to provide economical use of active materials without diminishing machine performance. Steel densities in the teeth and core assure acceptable levels of saturation, and allow the units to operate at +/- 10% of rated voltage without excessive iron loss.

Back to the top

 

Non-Reverse Assemblies

Non-reverse assemblies are installed whenever a reverse rotation caused by either an electrical phase reversal or pump reverse flow in an un-powered condition could cause damage to driven equipment. 

Continental, as an option for vertical motors utilizes a ratchet assembly with a locking pin design.  Clutch assemblies are available.  Continental Non-Reverse Assemblies are designed so that allowable direction of motor rotation can be changed in the field if necessary.

Back to the top

 

Rotor Construction

All Continental motors come with copper bar or aluminum die cast rotors.  Copper bar rotors provide our design engineers with the greatest flexibility in tailoring a motor to meet the customer needs. We can tailor the bar dimensions as well as copper composition to build a motor that meets your exact performance needs. As a standard, the motor is skewed for smooth starting and quiet operation.

Rotor slots are engineered to provide low inrush current while still providing superior starting and running torques.  The rotor is designed to have sufficient mass to handle the thermal effects seen during locked rotor and acceleration periods.  The end ring temperature rise is much less than the rotor bar allowing the end ring to act as a heat sink for the rotor bar losses.

Back to the top

 

Service Factor

All Continental motors are standard 1.15 service factor or can be quoted with 1.0SF when requested.

Back to the top

 

Shaft Construction

2 pole motors as standard will have shafts manufactured from C1045 normalized steel and will contain no welds. For API specifications forged shafts will be provided.

4 pole and slower motors will have shafts manufactured from C1045 steel and have stiffening ribs to insure critical speeds above rated speed.

Shaft diameters are selected to give a large safety factor in torsional shear strength. The complete rotor assembly is dynamically balanced.

Back to the top

 

Slot Combination

The slot combination selected for Continental motors provides minimum cusps in the motor speed-torque curves, and aids in magnetic noise suppression.

Back to the top

 

Stator Cores

Prime electrical grade silicon steel laminations are stacked in the stator frames for maximum electrical efficiency. The laminations are held in place with steel locking end-rings and full length keys. Additional support is supplied by sturdy press flanges and individual tooth stiffeners in larger motors. Semi-enclosed slots are used for the small ratings, and open slots for larger ratings. The stator core is ground to size to assure a uniform air gap between the core and the rotor.

Back to the top

 

Terminal Boxes

Constructed of cast iron or fabricated steel with sufficient room for connecting incoming leads. Boxes can be rotated in 90° increments. Motors of 600 volts or higher have auxiliary leads, including winding temperature detectors, bearing temperature detectors, and space heater leads brought to a separate terminal box.

Back to the top

 

Ventilation

Specially designed air circulation systems assure cool, long-life motors with maximum performance and efficiency. Each fan is individually balanced for proper air flow and for quiet, vibration-free operation.

Back to the top

 

Windings

Random and form-wound coils are placed in pre-insulated slots in the silicon steel cores. Coil extensions are individually tied with glass tape to rolled and welded brace rings to prevent movement caused by starting currents or line surges. After all connections are in place, the stator winding is impregnated in a vacuum pressure impregnation (VPI) system with an environmentally-sensitive varnish and then baked. This assures a homogenous, void-free bond between coils and frame.

Back to the top

 

Options

Continental motors can include a broad array of options designed to meet your most demanding operating conditions and specifications. A hort list of available options include:

  • Bearing and winding temperature monitoring
  • RTD’s (external access optionally available to bearing RTD’s)
  • Thermistors
  • Klixon thermostats
  • Thermocouples
  • Temperature relays
  • Bearing vibration switches and probes
  • Space heaters
  • Surge capacitors
  • Lightning arrestors
  • Current transformers
  • Differential protection
  • Zero speed switches
  • Encoders and tachometers
  • Motor mounted brakes
  • Oil Reservoir heaters
  • Oil Level Alarms
  • Hollow Shaft for all vertical ratings
  • With self release couplings if requested
  • Motor Saver
  • Special mounting dimensions
  • Features per API requirements
  • Name plate change
  • Additonla name plate
  • C Face
  • C Face with Inpro Seal
  • Change of rotation
  • Change to non-sparking fan
  • Short shaft
  • F1 or F2 mounting
  • Provisions for vertical jacking
  • Shaft grounding ring
  • Drip cover - cast iron
  • Drip cover - rolled steel
  • Provisions for vibration switch
  • Install encoder
  • Mill off motor feet
  • Installation of brake
  • Oversized conduit box

Back to the top

 

Continental Motor Frame Designations 

First Prefix  
N  Standard Squirrel Cage Motor, old NEMA and Larger then NEMA
SN  Wound Rotor, slip ring motor, old NEMA and Larger
SW Wound Rotor motor (NEMA 1952) 440 frames and smaller
W  Standard NEMA “U” frame
T  Standard NEMA “T” frame

 

Second and Third Prefix  
Mechanical Features  
B  Sleeve bearings used in motor
CA  Totally Enclosed Air to Air heat exchanger
CP  Explosion Proof, totally enclosed, not fan cooled
CW  Totally Enclosed Air to Water heat exchanger
F   TEFC
J  Weather Protected WPII
P  Explosion Proof, TEFC
U Dust Proof
V  Vertical
Z  Splash Proof

 

Electrical Features  
H  High torque, Low Starting Current
HR High Torque, High Slip (NEMA D)
L  Normal Torque, Low Starting Current

 

Suffix  
Mechanical features  
C  NEMA “C” Face
D  NEMA “D” Flange
U  Standard Long Shaft
Z  Special shaft dimensions
X  Special Mechanical modifications not covered by other letters
HSP  Hollow shaft

 Back to the top


Storage 

Short term storage (6 months or less) 

Store the motor, in it’s normal operating position, in a well ventilated, clean dry environment free from vibration and condensing humidity. Cover the motor with a tarp and energize the space heaters to keep the temperature of the winding a few degrees above the surrounding air. If the motor does not does not have space heaters, auxiliary heat should be used to keep the windings warm and free of condensation. 

Shaft should be rotated by hand every month to keep the bearings lubricated for rust and corrosion prevention and to change the position where the balls rest on the shaft to reduce the chance of brinelling. 

What is Brinelling?  Brinelling is the wear term used to describe surface damage of solids by repeated local impact or by static overload. The term  comes from a hardness testing procedure such as the (Brinell hardness test) which indents the surface being checked.

For long-term storage (long term storage is defined as over 6 months) 

Store the motor, in it’s normal operating position, in a well ventilated, clean dry environment free from vibration and condensing humidity. Cover the motor with a tarp and energize the space heaters to keep the temperature of the winding a few degrees above the surrounding air. If the motor does not have space heaters, auxiliary heat should be used to keep the windings warm and free of condensation. 

For grease lube motors, the grease cavity should be
completely filled with a moisture resistant grease for storage. For oil lube motors, fill the oil reservoir to it’s normal operational level.

The shaft should be rotated by hand every month to keep the bearings lubricated for rust prevention and to change the position where the balls rest on the shaft to reduce the chance of brinelling. 

Upon removal from storage 

The bearings should be inspected for corrosion and brinelling, prior to installation, and should be re-lubed with an appropriate amount and quantity of grease. 

The windings should be meggered before connecting on line. The reading should be approximately 2 megohms per each 1000 volts of operating voltage plus 1 megohm, corrected to 40 degrees C. 

Any reconditioning required, as noted by the inspections after removal from storage, should be performed prior to putting the motor into service. Reconditioning is not considered a warranty item.    Failure to follow these procedures may void the warranty.

Back to the top 

 

Continental Electric Motors Available Testing 

Test Rev-0 113003 

Routine test consists of the following:

           Measurement of Winding Cold Resistance (using digital VOM)
           No Load measurement of the following at rated voltage and frequency

                         
Current
                         
Power
                         
Nominal speed
           AC High-potential test per MG 1-20.48
           Locked Rotor test

                         
Measurement of locked rotor current and torque (at reduced voltage)
           No load vibration measurement per MG1-20.54
           Noise measurement
per IEEE 85 (no load, on sine wave power of rated
           voltage and frequency)
           DC Megger
           DC High Potential
           DC Surge 

 Complete test consists of the following:

Routine test per above
Full load temperature test
Full load speed measurement
Current balance check
Full load current check
Pull up torque – calculated
Breakdown torque measurement
Full load torque measurement
Efficiency vs load
Power factor vs load
Heat run
Load test
       Determination of efficiency and power factor at 100%, 75%, and 50% full load
       Determination of locked rotor power factor
       Determination of locked rotor and breakdown torque
Rated rotor temperature vibration test
 

API routine test consists of the following:

Routine test per above
Polarization index
Bearing temperature rise – sleeve bearings only
Bearing insulation check – if insulated bearings specified
Air gap measurement – sleeve bearings only
Shaft voltage and current measurement
Residual unbalance check
(note: 50Hz motors are tested at 60Hz)

  

Additional testing is available as follows:

No load vibration / mechanical run per API 4.3.3 
Heat run at maximum service factor for minimum of 4 hours

Bearing inspection – sleeve bearings only
Stator Testing
               
Stator core test
               
Surge test per IEEE 522
               
Special surge test on 2 sacrificial coils
               
Sacrificial coil – dissection and inspection
                Power Factor Tip-Up test
                Sealed winding conformance test (water spray)
Cold to hot vibration

               
Option 1 – after heat run
               
Option 2 – after multiple across the line starts
Tandem test
Unbalanced response test
Bearing housing natural frequency
Vibration tests with test or customer supplied half couplings
Frequency sweep
Soft foot
Inspect prior to VPI
Coast down critical speed search test
Residual Unbalance Check
(note: 50Hz motors are tested at 60Hz)

  

       Back to the top 

 